提高區(qū)域供冷系統(tǒng)能效與經(jīng)濟(jì)性的途徑

摘 要

摘要:分析了區(qū)域供冷系統(tǒng)的能效與經(jīng)濟(jì)性的影響因素。提出了提高區(qū)域供冷系統(tǒng)的能效與經(jīng)濟(jì)性的途徑:加大二級(jí)管網(wǎng)的供回水溫差、對(duì)二級(jí)管網(wǎng)進(jìn)行優(yōu)化設(shè)計(jì)、對(duì)區(qū)域供冷站進(jìn)行優(yōu)化

摘要:分析了區(qū)域供冷系統(tǒng)的能效與經(jīng)濟(jì)性的影響因素。提出了提高區(qū)域供冷系統(tǒng)的能效與經(jīng)濟(jì)性的途徑:加大二級(jí)管網(wǎng)的供回水溫差、對(duì)二級(jí)管網(wǎng)進(jìn)行優(yōu)化設(shè)計(jì)、對(duì)區(qū)域供冷站進(jìn)行優(yōu)化設(shè)計(jì)、對(duì)區(qū)域供冷系統(tǒng)進(jìn)行運(yùn)行優(yōu)化。
關(guān)鍵詞:區(qū)域供冷系統(tǒng);能效;經(jīng)濟(jì)性;優(yōu)化
Paths for Improving Energy Efficiency and Economy of District Cooling System
KANG Ying-zi,HUA Ben
AbstractThe factors influencing the energy efficiency and economy of district cooling system are analyzed. The paths for improving the energy efficiency and economy of district cooling system are put forward,they include increasing the temperature difference between supply and return water in secondary circuit,optimizing the design of secondary circuit,optimizing the design of district cooling station and optimizing the operation of district cooling system.
Key wordsdistrict cooling system;energy efficiency;economy;optimization
1 概述
   ① 當(dāng)前能源形勢(shì)
   近年來,我國能源消費(fèi)由于經(jīng)濟(jì)的快速發(fā)展而迅速增加。而我國的人均能源占有量遠(yuǎn)低于世界平均水平,特別是石油、天然氣人均資源量?jī)H為世界平均水平的7.7%、7.1%,能源供應(yīng)相對(duì)短缺。隨著經(jīng)濟(jì)的快速發(fā)展及城鄉(xiāng)居民消費(fèi)結(jié)構(gòu)升級(jí),能源供給與需求之間的缺口逐漸拉大,我國面臨嚴(yán)峻的能源形勢(shì)。
   我國的建筑能耗占總能耗的27.6%,并且將繼續(xù)增長(zhǎng)。建筑能耗中供暖空調(diào)的能耗占了很大的比重。對(duì)深圳15幢高層辦公建筑的能耗調(diào)查結(jié)果表明,空調(diào)能耗約占建筑總能耗的30%[1];對(duì)武漢9幢公共建筑的能耗調(diào)查和現(xiàn)場(chǎng)測(cè)試表明,空調(diào)能耗占建筑總能耗的22.3%~79.4%[2];對(duì)北京10幢大中型商場(chǎng)類建筑的能耗調(diào)查結(jié)果表明,空調(diào)能耗占建筑總能耗的40%~50%[3];對(duì)長(zhǎng)沙市14幢公共建筑的能耗調(diào)查結(jié)果表明,空調(diào)能耗占建筑總能耗的32.7%~64.3%,平均為46.65%[4]。因此,提高空調(diào)系統(tǒng)的能源利用效率迫在眉睫。冷(熱)量的梯級(jí)利用以及規(guī)模化設(shè)計(jì)是空調(diào)系統(tǒng)最有效的節(jié)能途徑。區(qū)域供冷是一種節(jié)能、經(jīng)濟(jì)、環(huán)保的空調(diào)技術(shù),也是空調(diào)節(jié)能的有效手段[5~8]
    ② 區(qū)域供冷系統(tǒng)存在的問題
    雖然區(qū)域供冷系統(tǒng)在國外已經(jīng)有很多成功運(yùn)行的工程實(shí)例,但目前某些區(qū)域供冷系統(tǒng)出現(xiàn)了造價(jià)、冷價(jià)較高的現(xiàn)象。究其原因,這些區(qū)域供冷系統(tǒng)主要存在著以下兩方面問題:
    a. 造價(jià)過高。導(dǎo)致區(qū)域供冷系統(tǒng)造價(jià)過高的原因主要有:區(qū)域供冷系統(tǒng)形式選擇不合理;冷負(fù)荷預(yù)測(cè)過大;區(qū)域供冷站內(nèi)各設(shè)備的配置不合理;二級(jí)管網(wǎng)的造價(jià)過高。這將極大地影響區(qū)域供冷系統(tǒng)的冷價(jià),也使得項(xiàng)目投資回收期較長(zhǎng)。
    b. 二級(jí)管網(wǎng)的造價(jià)與二級(jí)泵能耗過大。一些區(qū)域供冷工程的二級(jí)管網(wǎng)管徑偏大、冷水流量大溫差小、二級(jí)泵的功率大,最終導(dǎo)致二級(jí)管網(wǎng)的造價(jià)與二級(jí)泵能耗過大。
    ③ 能耗與經(jīng)濟(jì)性的影響因素
    區(qū)域供冷系統(tǒng)的造價(jià)主要包括區(qū)域供冷站內(nèi)制冷主機(jī)及其輔助設(shè)備的造價(jià)、二級(jí)管網(wǎng)造價(jià)。冷負(fù)荷的預(yù)測(cè),制冷主機(jī)的類型、容量、數(shù)量等是區(qū)域供冷站內(nèi)設(shè)備造價(jià)的主要影響因素。二級(jí)管網(wǎng)的造價(jià)主要受用戶與區(qū)域供冷站的距離、二級(jí)管網(wǎng)冷水供回水溫差等因素的影響。
    對(duì)區(qū)域供冷系統(tǒng)運(yùn)行能耗與費(fèi)用影響較大的因素包括:能源種類的選擇,應(yīng)盡可能利用低溫?zé)嵩础⒖稍偕茉?、天然?熱)源;制冷主機(jī)的選擇、主機(jī)與輔機(jī)的匹配程度;區(qū)域供冷系統(tǒng)的運(yùn)行策略。
2 提高能效與經(jīng)濟(jì)性的途徑
    ① 加大二級(jí)管網(wǎng)冷水的供回水溫差
    加大二級(jí)管網(wǎng)冷水的供回水溫差,降低二級(jí)管網(wǎng)的造價(jià)與二級(jí)泵的能耗。當(dāng)二級(jí)管網(wǎng)輸送的冷量相同時(shí),冷水供回水溫差越大,冷水流量越小。在一定流速范圍內(nèi),管徑越小,二級(jí)泵的功率也越小。因此,二級(jí)管網(wǎng)的造價(jià)與二級(jí)泵的能耗受冷水供回水溫差的影響很大。但是,冷水供回水溫差受制冷主機(jī)與空調(diào)末端的用冷特性的限制,不能隨意確定。
    目前,市場(chǎng)上的大部分制冷機(jī)組,在額定工況下的冷水進(jìn)出口溫差為5℃,也有少量制冷機(jī)組的溫差為8℃,極少數(shù)特殊設(shè)計(jì)的制冷機(jī)組溫差較大。通常,離心式制冷機(jī)組的冷水供回水溫差最低可到4℃,吸收式制冷機(jī)組可低至5℃。
    通常5~6℃的二級(jí)管網(wǎng)冷水供回水溫差稱為常規(guī)溫差,溫差超過7℃后稱為大溫差。目前,在國內(nèi)外的區(qū)域供冷工程中采用的二級(jí)管網(wǎng)冷水供回水溫差通常為6~11℃。文獻(xiàn)[9]推薦的二級(jí)管網(wǎng)冷水供回水溫差為7~11℃。北京中關(guān)村廣場(chǎng)區(qū)域供冷系統(tǒng)二級(jí)管網(wǎng)冷水供回水溫差為11.1℃,供水溫度低至1.1℃,采用了冰蓄冷技術(shù)[10]。上海東華大學(xué)松江校區(qū)區(qū)域供冷系統(tǒng)的二級(jí)管網(wǎng)冷水供、回水溫度為6、14℃,溫差為8℃[11]
    目前,常規(guī)空調(diào)系統(tǒng)末端的冷水供回水溫差為5℃,只有大溫差空調(diào)系統(tǒng)中空調(diào)末端的冷水供回水溫差才能達(dá)到8~10℃。以制冷機(jī)組作為冷源的空調(diào)系統(tǒng),由于受到制冷機(jī)組的限制,系統(tǒng)中冷水供回水溫差為5~10℃,只有利用冰蓄冷技術(shù)時(shí)系統(tǒng)的冷水供回水溫差才超過10℃。因此,在不考慮采用冰蓄冷技術(shù)的前提下,二級(jí)管網(wǎng)的冷水供回水溫差超過10℃時(shí),空調(diào)末端以及冷源必須進(jìn)行改造,關(guān)于這方面的分析詳見文獻(xiàn)[12]。
    在溫差為5~15℃內(nèi),二級(jí)管網(wǎng)的供回水溫差越大,二級(jí)管網(wǎng)的造價(jià)與二級(jí)泵的能耗越小。即使在對(duì)二級(jí)管網(wǎng)進(jìn)行優(yōu)化設(shè)計(jì)的情況下,供回水溫差仍對(duì)二級(jí)管網(wǎng)的造價(jià)與二級(jí)泵能耗有著極大的影響。
    康英姿[8]對(duì)某一區(qū)域供冷系統(tǒng)的二級(jí)管網(wǎng)在其他條件不變,分別在供、回水溫度為7、12℃,供、回水溫度為5、15℃,供回水溫度為5、19℃下,對(duì)二級(jí)管網(wǎng)的最優(yōu)設(shè)計(jì)方案的造價(jià)、能耗進(jìn)行了統(tǒng)計(jì)(見表1)。由表1可知,隨著供回水溫差的增大,二級(jí)管網(wǎng)造價(jià)、二級(jí)泵的能耗均大幅降低。將供回水溫差從5℃加大到14℃,二級(jí)泵年耗電量降低了58.6%,二級(jí)管網(wǎng)造價(jià)降低了46.6%,獲得很好的經(jīng)濟(jì)效果。
表1 二級(jí)管網(wǎng)的最優(yōu)設(shè)計(jì)方案的造價(jià)、能耗統(tǒng)計(jì)數(shù)據(jù)[12]
供回水溫差/
二級(jí)管網(wǎng)造價(jià)/元
二級(jí)泵造價(jià)/元
二級(jí)泵年耗電量/(kW·h·a-1)
二級(jí)泵年運(yùn)行費(fèi)用/
(元·a-1)
5
1163.42×104
181.81×104
81.43×104
79.00×104
10
746.06×104
106.18×104
47.64×104
46.02×104
14
621.20×104
79.26×104
33.71×104
31.35×104
   ② 對(duì)二級(jí)管網(wǎng)進(jìn)行優(yōu)化設(shè)計(jì)
   對(duì)二級(jí)管網(wǎng)進(jìn)行優(yōu)化設(shè)計(jì),提高二級(jí)管網(wǎng)的經(jīng)濟(jì)性。在管網(wǎng)的拓?fù)浣Y(jié)構(gòu)、各用戶冷負(fù)荷、供回水溫度均已知的情況下,二級(jí)管網(wǎng)的設(shè)計(jì)主要是確定管網(wǎng)內(nèi)各管段的管徑以及對(duì)二級(jí)泵的選型。
    工程中對(duì)于冷水系統(tǒng)常規(guī)的設(shè)計(jì)方法為假設(shè)流速法,該設(shè)計(jì)方法先依據(jù)工程經(jīng)驗(yàn)選取一個(gè)經(jīng)濟(jì)流速,按經(jīng)濟(jì)流速對(duì)整個(gè)管網(wǎng)的各管段進(jìn)行初步計(jì)算。然后對(duì)整個(gè)冷水系統(tǒng)進(jìn)行水力計(jì)算,最終確定各管段管徑及水泵的揚(yáng)程、流量并進(jìn)行水泵的選型。而優(yōu)化設(shè)計(jì)方法以壽命期費(fèi)用最小為目標(biāo),在綜合考慮二級(jí)管網(wǎng)造價(jià)與二級(jí)泵的運(yùn)行能耗的基礎(chǔ)上,對(duì)二級(jí)管網(wǎng)進(jìn)行設(shè)計(jì),確定經(jīng)濟(jì)性最優(yōu)的各管段管徑、二級(jí)泵的揚(yáng)程、流量、型號(hào)。
   由于優(yōu)化設(shè)計(jì)綜合考慮了二級(jí)管網(wǎng)的造價(jià)與運(yùn)行費(fèi)用兩個(gè)方面,以壽命期總費(fèi)用最小作為目標(biāo),對(duì)二級(jí)管網(wǎng)進(jìn)行設(shè)計(jì)。因此,與常規(guī)的設(shè)計(jì)方法相比,能提高二級(jí)管網(wǎng)的經(jīng)濟(jì)性。此外,由于區(qū)域供冷系統(tǒng)的二級(jí)管網(wǎng)輸送的冷量大、距離遠(yuǎn),造價(jià)與運(yùn)行費(fèi)用較高,對(duì)其采用優(yōu)化設(shè)計(jì)方法進(jìn)行設(shè)計(jì),可避免因二級(jí)管網(wǎng)設(shè)計(jì)的先天不足導(dǎo)致的造價(jià)過高或二級(jí)泵能耗過大等缺點(diǎn)。
   ③ 對(duì)區(qū)域供冷站進(jìn)行優(yōu)化設(shè)計(jì)
   對(duì)區(qū)域供冷站進(jìn)行優(yōu)化設(shè)計(jì),提高區(qū)域供冷系統(tǒng)的經(jīng)濟(jì)性。區(qū)域供冷站是區(qū)域供冷系統(tǒng)的核心部分,不僅造價(jià)高,而且也是能耗主體。區(qū)域供冷站的設(shè)計(jì)主要是確定制冷主機(jī)及其輔助設(shè)備的類型、容量、數(shù)量。由于區(qū)域供冷系統(tǒng)負(fù)擔(dān)的用戶多,各用戶的冷負(fù)荷隨室外氣象參數(shù)及內(nèi)部的用冷特性不斷變化,制冷主機(jī)及其輔助設(shè)備種類與型號(hào)眾多。因此,區(qū)域供冷站內(nèi)設(shè)備選型的可行方案很多。但是,各可行方案的造價(jià)、運(yùn)行能耗與費(fèi)用各異,在這些眾多的可行方案中選擇一個(gè)作為最終方案是區(qū)域供冷站設(shè)計(jì)工作的難點(diǎn)。
   區(qū)域供冷站的經(jīng)濟(jì)性評(píng)價(jià)涉及造價(jià)、運(yùn)行費(fèi)用。因此,在設(shè)計(jì)階段,必須對(duì)區(qū)域供冷站各可行方案的造價(jià)與運(yùn)行費(fèi)用進(jìn)行權(quán)衡,最終找出最優(yōu)的方案,使得區(qū)域供冷站在壽命期內(nèi)的經(jīng)濟(jì)性達(dá)到最優(yōu)。關(guān)于區(qū)域供冷站的優(yōu)化設(shè)計(jì),由于區(qū)域供冷系統(tǒng)的復(fù)雜性,應(yīng)該在對(duì)區(qū)域供冷站的運(yùn)行與設(shè)計(jì)建模的基礎(chǔ)上,對(duì)其進(jìn)行求解才可能實(shí)現(xiàn)。
   通過對(duì)區(qū)域供冷站進(jìn)行優(yōu)化設(shè)計(jì),使其在整個(gè)壽命期內(nèi)的經(jīng)濟(jì)性達(dá)到最優(yōu),從根本上避免出現(xiàn)因設(shè)計(jì)不合理而導(dǎo)致的區(qū)域供冷系統(tǒng)先天性的造價(jià)過高及運(yùn)行能耗過大問題,實(shí)現(xiàn)了區(qū)域供冷站內(nèi)部各設(shè)備的選型的科學(xué)性,從而保證了區(qū)域供冷系統(tǒng)的經(jīng)濟(jì)、節(jié)能優(yōu)勢(shì)能得到發(fā)揮。
   ④ 對(duì)區(qū)域供冷系統(tǒng)進(jìn)行運(yùn)行優(yōu)化
   對(duì)區(qū)域供冷系統(tǒng)進(jìn)行運(yùn)行優(yōu)化,提高區(qū)域供冷系統(tǒng)的運(yùn)行效率,降低運(yùn)行費(fèi)用。由于氣象參數(shù)的變化、用戶用冷特性的差異與不確定性,區(qū)域供冷系統(tǒng)的冷負(fù)荷處在動(dòng)態(tài)變化之中。因此,需要確定區(qū)域供冷系統(tǒng)的運(yùn)行策略以適應(yīng)冷負(fù)荷的變化。
    區(qū)域供冷系統(tǒng)設(shè)備多、冷水輸送系統(tǒng)復(fù)雜,整個(gè)系統(tǒng)的運(yùn)行效率與運(yùn)行費(fèi)用受較多因素的影響。其中影響較大的因素主要有:制冷機(jī)組的運(yùn)行效率、二級(jí)泵的運(yùn)行效率、能源(包括電力與熱源)價(jià)格。這些因素的變化都將影響區(qū)域供冷系統(tǒng)的運(yùn)行效率、運(yùn)行費(fèi)用。因此,對(duì)于區(qū)域供冷這樣的復(fù)雜系統(tǒng),應(yīng)根據(jù)變化的能源價(jià)格、冷負(fù)荷等外部邊界條件,以運(yùn)行效率最高或運(yùn)行費(fèi)用最小為目標(biāo),對(duì)區(qū)域供冷系統(tǒng)的運(yùn)行進(jìn)行優(yōu)化。通過運(yùn)行優(yōu)化最終確定區(qū)域供冷系統(tǒng)的運(yùn)行策略(系統(tǒng)內(nèi)各設(shè)備的實(shí)際容量與運(yùn)行負(fù)荷率、各設(shè)備的啟停狀況),從而控制區(qū)域供冷系統(tǒng)的總能耗與運(yùn)行費(fèi)用,提高區(qū)域供冷系統(tǒng)的運(yùn)行效率,降低運(yùn)行費(fèi)用。
3 結(jié)論
    提高區(qū)域供冷系統(tǒng)的能效與經(jīng)濟(jì)性的有效措施:加大二級(jí)管網(wǎng)冷水的供回水溫差,降低二級(jí)管網(wǎng)的造價(jià)與二級(jí)泵的能耗;對(duì)冷水二級(jí)管網(wǎng)進(jìn)行優(yōu)化設(shè)計(jì),提高二級(jí)管網(wǎng)的經(jīng)濟(jì)性與能效;對(duì)區(qū)域供冷站進(jìn)行優(yōu)化設(shè)計(jì),提高區(qū)域供冷系統(tǒng)經(jīng)濟(jì)性。對(duì)區(qū)域供冷系統(tǒng)進(jìn)行運(yùn)行優(yōu)化,提高區(qū)域供冷系統(tǒng)的運(yùn)行效率,降低運(yùn)行費(fèi)用。
    采用上述措施,將進(jìn)一步提高區(qū)域供冷系統(tǒng)的能效與經(jīng)濟(jì)性,避免實(shí)施中出現(xiàn)的問題,使得區(qū)域供冷系統(tǒng)的優(yōu)勢(shì)能得到充分地發(fā)揮,為我國的節(jié)能減排工作作出貢獻(xiàn)。
參考文獻(xiàn):
[1] 梁珍,趙加寧,郭駿.高層辦公建筑能耗調(diào)查與節(jié)能潛力分析[J].節(jié)能技術(shù),2001,(1):19-22.
[2] 李玉云,張春枝,曾省稚.武漢市公共建筑集中空調(diào)系統(tǒng)能耗分析[J].暖通空調(diào),2002,(4):85-87.
[3] 薛志峰,江億.商業(yè)建筑的空調(diào)系統(tǒng)能耗指標(biāo)分析[J].暖通空調(diào),2005,(1):37-41.
[4] 楊昌智,吳曉艷,李文菁,等.長(zhǎng)沙市公共建筑空調(diào)系統(tǒng)能耗現(xiàn)狀與節(jié)能潛力分析[J].暖通空調(diào),2005,(12):39-43.
[5] 壽青云,陳汝東.壽命周期成本分析在區(qū)域供冷供熱評(píng)價(jià)的應(yīng)用[J].煤氣與熱力,2006,26(4):51-54.
[6] 康英姿,華賁.區(qū)域供冷系統(tǒng)與燃?xì)夥植际侥茉聪到y(tǒng)的結(jié)合[J].煤氣與熱力,2007,27(2):62-66.
[7] 張朝輝,李震,端木琳.區(qū)域供冷技術(shù)的應(yīng)用與技術(shù)條件[J].煤氣與熱力,2007,27(3):86-89.
[8] 康英姿,華賁.區(qū)域供冷系統(tǒng)的技術(shù)與經(jīng)濟(jì)性分析[J].煤氣與熱力,2007,27(11):79-82.
[9] ASHRAE.2004 ASHRAE handbook-system and equipment[M].Atlanta:American Society of Heating,Refrigerating and Air-Conditioning Engineers Inc.,2004.
[10] 趙建成,牛利敏,張志毅.低溫送風(fēng)空調(diào)設(shè)計(jì)實(shí)例研究與經(jīng)濟(jì)性分析[J].北京工業(yè)大學(xué)學(xué)報(bào),2006,(10):922-924.
[11] 李豫,黃璞潔,胡文斌,等.東華大學(xué)松江校區(qū)蓄能方式下的區(qū)域供冷系統(tǒng)設(shè)計(jì)[J].中國建設(shè)信息供熱制冷,2005,(3):27-31.
[12] 康英姿.區(qū)域供冷系統(tǒng)集成建模與優(yōu)化設(shè)計(jì)(博士學(xué)位論文)[D].廣州:華南理工大學(xué),2008.
 
(本文作者:康英姿1 華賁2 1.華南理工大學(xué) 機(jī)械與汽車工程學(xué)院 廣東廣州 510641;2.華南理工大學(xué) 強(qiáng)化傳熱與過程節(jié)能教育部重點(diǎn)實(shí)驗(yàn)室 廣東廣州 510641)